A quick vlog on how to calibrate the touch screen on a Beijer QTERM HMI using the Service Menu (which allows modification of system parameter such as IP Address, Date and Time, Calibrate Touch, Erase Project).

In order to access the Beijer Service Menu (to calibrate the Beijer QTERM touch screen), these are the steps you will have to follow
1) Apply power to the pane
2) Touch and hold the touch screen when the white background appears
3) The touch screen will prompt you again to touch the screen, release and touch the screen again.
4) From the Service Menu, select Touch Calibrate button. Follow the instructions on the screen.

You will be required to touch the 4 corners of the touch screen and the center screen. This will be required to be done twice.

The touch calibration function will requre keyboard as you will be required to hit the Enter key to accept the new calibration.

Watch my vlog and it is much clearer.